Britton Electronics & Automation Inc.
Expert Design, Automation Programming & System Integration

Troubleshooting beyond the alarm

A PLC Fault Is Usually the Symptom, Not the Diagnosis

A fever tells you something is wrong. It does not tell you what caused it. A PLC fault works the same way. It is a signal, not an answer. Clear it without understanding it, and the underlying problem may still be there.

The fault is telling the truth

Clearing a fault can restore operation, but it does not prove the underlying condition is gone. The device reporting the problem is not necessarily the device causing it. Good troubleshooting separates where the symptom appeared from where the failure began.

The fault told the truth. It just did not tell the whole truth.

Industrial control system signal transient visualization illustrating a brief disturbance behind a PLC fault

A brief signal transient can reveal itself at the PLC even when the initiating condition began elsewhere in the control system.

Follow the failure backward

Start with the alarm, then trace the conditions that could have produced it. Check the power feeding the circuit, signal behavior, field wiring, communications path, and the process condition the controller expected to see.

The objective is to identify the first abnormal condition, not simply the last device that complained.

A card replacement that did not hold

At one facility, several analog readings began dropping out for an instant, jumping to full scale within milliseconds, then settling back down. The analog input card was the obvious suspect. It was replaced, the fault cleared, and the system returned to service.

A few days later, the same symptom returned on a different card. That recurrence changed the question from "Which card failed?" to "What are these cards seeing that they should never see?"

The actual cause

The 24 VDC field power supply feeding the I/O circuits had begun to degrade. Its output became unstable under load. Those disturbances reached the analog circuitry and produced momentary dropouts followed by full-scale readings.

The event was fast enough to resemble noise on a trend and fast enough that a technician standing at the panel with a meter could easily miss it. Replacing the power supply stopped the problem because the failed component was finally identified.

The same pattern appears across a control system

Drive fault

The drive reports the condition, while the cause may be a mechanical load, unstable input power, wiring issue, or process demand.

Unreliable sensor

The sensor gets blamed, while damaged wiring, poor shielding, electrical noise, or unstable field power may be changing the signal.

Remote I/O dropout

The rack goes offline, while the initiating problem may be a switch, cable, connector, radio path, or upstream power supply.

Controller communications fault

The PLC becomes unresponsive, while malformed, incomplete, or excessive traffic elsewhere on the network may be consuming limited communications resources.

Questions that move the diagnosis forward

  • What changed immediately before the event?
  • Is control and field power stable under the actual load?
  • Are the I/O signals behaving normally at the source and at the module?
  • Are field devices communicating correctly?
  • Is the network healthy, or merely connected?
  • Is the process reaching the position, pressure, level, speed, or state the PLC expects?
  • What evidence remains after the fault is reset?

A reset is a recovery step, not a root cause

Replacing the component named in an alarm is not always troubleshooting. A system returning to normal after a reset does not mean the cause disappeared. Preserve event history, capture trends at useful time resolution, and test the full signal and power path before declaring the issue resolved.

How can BEA help?

BEA can help trace intermittent PLC, I/O, power, drive, and industrial network problems across the system instead of stopping at the first alarm. We support evidence-based troubleshooting, application review, component selection, and corrective planning so the same symptom does not keep returning.

Bring us the fault history, trend data, recent changes, and what has already been tested. We will help turn the alarm into a practical diagnostic path.


Industrial Cybersecurity

Industrial Cybersecurity Myths We Still Encounter in the Field

The most important improvements often begin with correct network design, clear access paths, and layered protection.

Industrial cybersecurity article cover illustrating secure connected operations
Industrial cybersecurity depends on understanding every trusted path into the control environment.

The problem often starts before a security appliance is installed

After a major cyberattack, the first questions often focus on firewalls, software, or the newest security product. Those tools have a place, but many significant improvements cost little. They begin with designing industrial networks correctly and challenging assumptions about how systems are connected.

Manufacturers, municipalities, water systems, and other industrial facilities can take security seriously and still carry hidden risk when trusted devices or support processes create overlooked pathways.

Five myths worth challenging

Myth 1: Our PLC is not connected to the Internet

The PLC may have no direct Internet connection, while an engineering workstation, HMI, remote support computer, historian, reporting server, cloud dashboard, or vendor remote-access package does.

An attacker may only need access to a trusted device that already communicates with the PLC. Map every pathway into the control network, not only the PLC's public exposure.

Myth 2: We have a firewall, so we are secure

A firewall is an important layer, but it is not the complete architecture. Effective protection can include VPN-only remote access, strong authentication, segmentation, least privilege, secure support procedures, logging, monitoring, and routine maintenance.

Design the system so other protections continue to reduce risk if one layer fails.

Myth 3: We are too small to be a target

Small manufacturers, municipal water and wastewater systems, grain facilities, and local industries can all experience cyber incidents. Many attacks are automated and search broadly for vulnerable systems.

Organization size does not remove exposure. Security posture and reachable pathways matter.

Myth 4: Our vendor handles cybersecurity

Equipment, network, and firewall manufacturers can provide capable components, but no single vendor automatically knows how the entire facility is connected.

Security comes from integrating devices, networks, remote connections, engineering workstations, and support processes correctly. That is an engineering responsibility.

Myth 5: Nothing has happened, so we must be secure

Years without a known incident do not prove that the architecture is secure. An exposed path may simply remain undiscovered.

Preventive cybersecurity works like preventive maintenance: remove unnecessary risk before it affects operations.

Good security should support daily work

Operators still need to operate. Maintenance personnel still need to troubleshoot. Authorized engineers still need to provide support. A properly designed system preserves those workflows while preventing unauthorized access.

The objective is not complexity or fear. It is thoughtful engineering: understand communications, limit unnecessary exposure, plan remote access, and build multiple layers of protection around the people and infrastructure that depend on the system.

How can BEA help?

BEA can help industrial teams review network pathways, remote-access practices, segmentation needs, engineering workstations, and support workflows. The goal is a practical security approach that protects operations without obstructing authorized users.

Read the original source article for the full field perspective.


Municipal OT security guidance

Minnesota water-system cyberattacks reinforce the need for VPN-only remote access

Remote communications are essential to modern water and wastewater operations. When traffic crosses infrastructure the municipality does not control, the connection must protect itself.

Municipal water tower representing Minnesota public water infrastructure

A warning for every municipal utility

A coordinated cyberattack targeted operational technology at more than 30 Minnesota community water systems on July 26 and 27, 2026. State incident-response teams worked with federal, state, local, Tribal, and private-sector partners. Officials reported limited or mitigated effects in communities that disclosed incidents, with no active request for residents to change normal drinking-water use.

Plymouth reported communication outages affecting two water towers and multiple wastewater lift stations while crews continued through manual procedures. The city also said the issue was limited to equipment connected through cellular communications.

That detail does not establish that a cellular carrier was compromised or that cellular technology caused the attack. The initial access method, affected equipment, account, vulnerability, and responsible organization had not been publicly identified.

The BEA standard

Whenever municipal operational-technology traffic crosses a third-party network, it should pass through an encrypted VPN and terminate at a properly configured firewall.This applies both to a person viewing or servicing a system remotely and to two municipal facilities exchanging process data.

Cellular service is transport, not a security boundary

Cellular communications can be reliable and secure for towers, wells, lift stations, pump stations, and other remote facilities. But a modem does not automatically protect the PLC behind it. A private IP address is not encryption, a private carrier network is not a firewall, and a private access-point name does not eliminate the need for authentication and access restrictions.

Protect the path

Use a maintained VPN with strong encryption and authenticated endpoints whenever OT traffic crosses a cellular carrier, internet provider, leased circuit, cloud service, or other external network.

Protect the destination

Terminate the connection at a firewall or secure gateway and permit only the required source, destination, protocol, port, user, device, site, purpose, and access period.

Protect the account

Use individual accounts, strong authentication, multifactor authentication where practical, connection logging, controlled account lifecycle management, and prompt removal of obsolete access.

Protect operations

Segment control and business networks, maintain current firmware and security updates, document the architecture, and preserve tested manual operating procedures.

Treat third-party networks as untrusted

“Untrusted” does not mean the service provider is acting improperly. It means the utility does not control every router, support account, platform, configuration, subcontractor, maintenance process, or security decision along the route. Design as though the path between trusted endpoints could be observed, scanned, interrupted, or misconfigured.

Examples

  • Cellular and public internet connections
  • Cable, fiber, or DSL internet services
  • Third-party leased circuits
  • Shared municipal or county networks
  • Cloud-managed or vendor remote-access platforms
  • Third-party-owned or unmanaged radio networks

Utility-owned radio is different

A properly designed municipal radio network may remain a trusted internal system when the utility owns, programs, maintains, and controls its radios, frequencies, addressing, sites, and permitted participants. It still requires review, segmentation, documentation, and least-privilege access.

Remote viewing is remote access

An operator checking SCADA from home, an engineer troubleshooting a pump, an integrator reviewing PLC logic, and a technician examining an HMI or VFD all represent remote access to critical infrastructure.

Authorized computer → encrypted VPN → municipal firewall → specifically approved internal system

Do not directly expose PLC programming interfaces, HMI web servers, SCADA servers, Remote Desktop, VNC, industrial-router administration, engineering software services, camera interfaces, building controls, or unprotected equipment web interfaces to the public internet.

Site-to-site traffic needs the same protection

A tower reporting to a plant, a lift station sending alarms to SCADA, or a well station exchanging pressure and pump data is also remote access when the path crosses an external network.

Remote PLC network → remote-site firewall → encrypted VPN → central-site firewall → SCADA network

The PLC and HMI remain on a private local network. Authenticated firewalls establish the encrypted tunnel and permit only the specific process traffic required. The provider transports the tunnel; it does not become part of the trusted control system.

Encryption and firewalling perform different jobs

Encryption protects the path

It helps prevent operational data and credentials from being observed or altered while traffic crosses infrastructure outside the utility's control.

The firewall protects the destination

It prevents an encrypted tunnel from becoming a broad bridge into the control network by limiting exactly what the connection may reach.

Federal standards follow the same security principle

Federal agencies routinely send information across commercial internet providers, telecommunications carriers, cloud platforms, and other infrastructure they do not fully own or control. Federal security policy does not treat those third-party networks as the protection boundary. Sensitive traffic must instead be protected using approved cryptography and secure communications methods.

Validated cryptography

FIPS 140-3 establishes security requirements for cryptographic modules operated by federal agencies or on their behalf. The NIST validation program verifies that modules meet the standard.

Protected communications

NIST guidance identifies TLS for protecting approved application and web traffic across the internet. NIST also describes IPsec VPNs as a means to provide confidentiality, integrity, authentication, replay protection, and access control for network-to-network traffic.

Trust-boundary controls

CISA's Trusted Internet Connections guidance reinforces that protections must remain in place when federal systems connect with remote users, cloud services, and external networks. It does not require one technology for every connection, but an outside carrier or cloud provider should not automatically become part of the trusted network.

When traffic crosses infrastructure an organization does not fully own and control, the traffic must protect itself.These federal requirements do not automatically apply as legal mandates to every municipal utility, but they demonstrate an established security principle. For water and wastewater systems, remote operator and vendor access should pass through an authenticated VPN, site-to-site communications should use encrypted VPN tunnels, and every third-party connection should terminate at a properly configured firewall. TLS can protect approved web applications, but a public-facing SCADA webpage should never replace a secured VPN and controlled access path.

Field checks for municipal teams

Inventory access

  • Who can connect remotely today?
  • Which systems can each person reach?
  • Are accounts individual and current?
  • Can access be disabled immediately?

Review boundaries

  • Does every external path terminate at a firewall?
  • Are site-to-site links encrypted?
  • Are rules limited to required traffic?
  • Are OT and business networks segmented?

Verify resilience

  • Are connections logged and reviewed?
  • Are firmware and VPN software maintained?
  • Are configurations and backups documented?
  • Can crews operate locally when communications fail?

Manual operation remains essential

Utilities should be prepared to operate when SCADA communications, cellular service, telemetry, or internet access is unavailable. Practice local starting and stopping, independent level and alarm checks, chemical-feed control, manual process recording, cross-site communications, and controlled restoration before an emergency occurs.

How Britton Electronics & Automation can help

BEA designs, supports, and services automation systems for municipal water and wastewater facilities. We can help review remote-access paths, identify internet-exposed equipment, secure cellular-connected sites, configure site-to-site VPNs, review firewall rules, segment networks, restrict vendor access, remove obsolete accounts, assess utility-owned radio networks, document PLC/HMI/SCADA configurations, and develop practical backup, recovery, and manual-operation plans.

The goal is not to eliminate useful connectivity. It is to make every remote connection deliberate, authenticated, encrypted, restricted, logged, maintained, and capable of being disabled without preventing safe operation.

Further guidance: Minnesota Department of Health: Assessing Security of Public Water Systems · CISA: Protecting remotely accessible industrial controllers


BEA motor-connection practice

Why BEA standardizes on Polaris connectors for motor leads over 2 hp

A pre-insulated, torque-applied connector gives our field teams a cleaner and more repeatable alternative to wire nuts and field-taped split bolts on larger motor connections.

NSI Polaris pre-insulated multi-port connector
Official NSI Polaris pre-insulated connector image.

The field problem

Larger motor-lead junctions need a connection method that fits the actual conductor count, conductor size, enclosure, and service environment. Wire nuts are not BEA's preferred standard for these larger connections, while split bolts add a separate field-insulation process.

A Polaris connector combines the mechanical termination and insulated body in one selected assembly. Prepared conductors are inserted and the covered pressure screws are tightened to the manufacturer's specified torque.

Why the standard matters

Less field insulation work

Pre-insulated connectors avoid the multi-layer tape build-up normally required to insulate an exposed split-bolt connection after termination.

Repeatable torque process

Technicians can follow the installation instructions and apply the specified torque, making the termination process easier to standardize and inspect.

Better fit for multiple leads

Polaris models are available with multiple ports. The selected model must be verified for the required conductor count and sizes rather than assuming a split bolt is listed for a multi-conductor junction.

Cleaner service access

A contained connector body keeps the junction organized for inspection, troubleshooting, motor replacement, and future maintenance.

Why split bolts are a poor fit for this motor practice

Listing and conductor count

BEA does not assume a split bolt can accept more conductors than its listing permits. Many motor-lead junctions require a configuration beyond a simple two-conductor splice, so the exact listed use has to be checked.

Taping labor

The completed connection needs careful insulation build-up, finish wrapping, and inspection. That adds time and depends heavily on field workmanship.

Vibration exposure

Motors and nearby industrial equipment can transmit vibration. If tape is not built up and protected adequately, movement can abrade the insulation over time.

Designer and installer checks

  • Choose the connector from actual conductor size, type, class, and count—not motor horsepower alone.
  • Confirm the selected model's listing and suitability for the enclosure and dry, wet, or exposed environment.
  • Check available junction-box space, bend radius, and future maintenance access.
  • Use the manufacturer's strip length, port-plug, and torque instructions.
  • Account for vibration and inspect the completed connection before energizing equipment.

How can BEA help?

BEA can help review motor connection standards, identify the appropriate Polaris connector configuration, and coordinate conductor, enclosure, environmental, vibration, and maintenance requirements for the application.

Manufacturer source: NSI Polaris connector solutions and NSI guidance on pre-insulated connectors.


Blue Ribbon wastewater instrumentation from BEA

Durable level measurement for demanding wastewater service

Blue Ribbon Corp points to more than four decades in wastewater management and positions its BC001 Birdcage as a long-service instrument for challenging environments. BEA is a Blue Ribbon distributor and can support product selection and application planning.

Blue Ribbon BC001 Birdcage wastewater level instrument
Blue Ribbon's BC001 Birdcage for wastewater level-measurement applications.

The operating challenge

Wastewater facilities need dependable level information while managing exposure, access, weather, electrical disturbances, and maintenance constraints. A failed or unstable measurement point can complicate pump control, alarm response, and service scheduling.

Blue Ribbon emphasizes durability and lifecycle value for the Birdcage. Actual service life depends on the process, installation, environment, protection strategy, and maintenance practices, so application review remains important.

What stands out

Wastewater focus

Blue Ribbon presents the BC001 Birdcage as its flagship solution for wastewater management and cites long experience serving these applications.

Lifecycle perspective

The manufacturer frames product value around longevity, reduced replacement frequency, and less downtime rather than initial purchase price alone.

Surge-protection option

Blue Ribbon identifies the BCP3000 Birdcage Series surge protector as the companion option for addressing lightning-related damage and ties it to enhanced warranty coverage.

What this means for plant teams

Plan for the full measurement point

Instrument choice, mounting, wiring, control integration, environmental exposure, and surge protection should be considered together.

Compare lifecycle cost

Review expected service demands, access costs, downtime exposure, spares, and replacement labor alongside acquisition cost.

Validate the application

Confirm process conditions and required performance with current manufacturer documentation before final selection.

Selection and implementation checks

Define the duty

Document the level range, process media, mounting location, access limitations, environmental conditions, and required control response.

Review electrical protection

Evaluate grounding, wiring routes, panel protection, and whether the BCP3000 option belongs in the overall lightning and surge strategy.

Confirm current terms

Verify product configuration, compatibility, warranty conditions, and installation requirements against current Blue Ribbon documentation.

How can BEA help?

BEA distributes Blue Ribbon products and can help wastewater operators, engineers, and system integrators review the BC001 Birdcage and related protection options for a specific measurement point. Our role is to connect product information with the real installation constraints that drive a supportable selection.

Read Blue Ribbon Corp's wastewater management article


Turck product news

Keep the analog sensor. Add an IO-Link path.

Turck's ILC Analog to IO-Link Inline Converter gives facilities a compact retrofit option when an existing analog sensor remains suitable but the controls strategy calls for IO-Link connectivity.

Turck ILC analog to IO-Link inline converter
Turck ILC inline converter for analog-sensor retrofit applications.

The modernization problem

Moving a machine or process area toward IO-Link does not always require replacing every field sensor. The ILC sits between a compatible analog sensor and an IO-Link master, converting the sensor signal for the IO-Link environment.

That approach can help retain an established sensing point while creating a more consistent digital connection upstream. The application still needs a compatibility review; the converter does not remove the need to verify signal type, power, connector arrangement, and master configuration.

What Turck's converter adds

Analog input flexibility

Turck lists adjustable current inputs of 0-20 mA and 4-20 mA, plus voltage ranges of 0-5 V, 1-6 V, and 0-10 V.

Inline installation

The cylindrical M12-format device connects directly to an analog sensor through its 300 mm lead and provides an M12 IO-Link connection toward the master.

Parameterization options

The converter is parameterizable through IO-Link, including use with Turck Automation Suite. Turck also identifies optional timer delays and switching-output functions for alarm or trip-amplifier use.

Operational implications

Phased upgrades

A converter can support staged modernization when wholesale sensor replacement is unnecessary or impractical.

Configuration consistency

IO-Link parameterization can bring the converted point into the same engineering workflow as other IO-Link devices.

Application review remains essential

Signal range, wiring, environmental conditions, power budget, IO-Link master behavior, and required control response must be checked before selection.

Designer and implementation checks

Confirm the signal

Match the sensor's current or voltage output to a supported input range and confirm the required scaling in the control system.

Check the physical interface

Review M12 pinout, cable length, mounting space, strain relief, ingress protection, and the ambient-temperature range for the installation.

Plan commissioning

Confirm the master's IO-Link port configuration, IODD handling, process-data mapping, diagnostics, and any switching or timing behavior before production release.

How can BEA help?

BEA can help evaluate whether the Turck ILC is a good fit for an existing analog sensing point, review the connection to the selected IO-Link master, and support parameterization and commissioning planning. Final selection should be based on the sensor signal, electrical design, environmental requirements, and machine or process risk.

Read Turck's product announcement  |  Review the official product details


Industrial reliability and municipal controls

Surge Protection: Why Industrial and Municipal Facilities Cannot Afford to Ignore It

Modern plants, pump stations, lift stations, well houses, and utility systems depend on electronics that are productive, diagnostic-rich, and vulnerable to short electrical disturbances. A transient event that lasts only a fraction of a second can damage a PLC, corrupt communications, trip a drive, or leave a field device weakened enough to fail later.

DIN rail surge protective devices for North American power supply configurations
Surge protection is normally selected in layers, from service and distribution equipment down to control panels, signals, and remote devices.

Illustration: how a surge protector works

When voltage rises suddenly, the surge protective device provides a preferred path for transient energy. It clamps the overvoltage and diverts surge current toward the grounding and bonding system, helping keep the remaining voltage at the protected equipment within a safer range for the application.

Normal operation

The SPD remains inactive while system voltage is within its intended operating range.

During the transient

The SPD conducts surge current and limits the voltage passed downstream. The exact protection depends on device selection and installation.

After the event

Status indicators, alarm contacts, or replaceable modules should be checked so the site is not left unknowingly unprotected.

What a surge is

An electrical surge, or transient overvoltage, is a brief voltage increase above the normal operating level. A surge protective device limits that transient energy by diverting or restricting surge current before it reaches vulnerable electronics.

Where it comes from

Lightning is only one source. Utility switching, motor starts and stops, contactors, solenoids, VFDs, capacitor banks, generator transfers, faults, and long outdoor conductors can all place surge energy into a facility.

Why it matters

Industrial and municipal systems combine sensitive controls, inductive loads, long cable runs, outdoor equipment, and remote structures. That mix gives transient voltage many possible entry paths.

Protecting only the main feed is not enough

A surge can enter through any connected conductor. Main power protection may reduce one exposure, but it does not automatically protect a level transmitter, Ethernet cable, telephone circuit, radio coax, buried instrumentation line, or remote I/O connection.

Municipal sites

  • Lift stations and well houses
  • Pump control panels and VFDs
  • Flow, pressure, and level transmitters
  • Cellular, licensed radio, and antenna systems

Industrial sites

  • PLC and HMI cabinets
  • Machine panels and MCCs
  • Ethernet and serial communication networks
  • Remote instruments and interbuilding wiring

Surge damage is not always immediate

Some events create obvious failures: a power supply stops, a PLC fails, or a drive refuses to restart. Other events weaken components and create problems that are harder to connect to the original disturbance.

Control symptoms

Intermittent PLC faults, unexpected HMI or computer reboots, failed I/O channels, and repeated power-supply failures can all follow transient exposure.

Signal symptoms

Drifting analog readings, unstable instrument signals, damaged Ethernet ports, radio failures, and unexplained communication losses can consume troubleshooting time long after the event.

Process risk

For water, wastewater, utility, and production systems, the cost is not limited to replacement hardware. Downtime, emergency service, data loss, regulatory impact, or process interruption may be the larger concern.

A UPS is not a complete surge-protection system

A UPS is useful for ride-through power and controlled shutdown. It should not be treated as a substitute for properly selected surge protective devices, grounding, bonding, circuit protection, and electrical-system design.

A layered approach is normally required

1. Service and distribution

Protection near the incoming service or primary distribution equipment helps reduce larger transient events entering from the utility or facility distribution system.

2. Branch and control panels

Additional devices at distribution panels, MCCs, pump panels, machine panels, and automation cabinets place protection closer to PLCs, drives, HMIs, power supplies, and network equipment.

3. DC power and signals

Low-voltage circuits may need separate protection for 24 VDC power, analog loops, digital I/O, RTDs, thermocouples, Ethernet, serial communication, telephone lines, and radio coax.

4. Remote equipment

Long outdoor runs and cables between structures often deserve attention at both ends so field devices and panels are not left exposed from the remote side.

Panel and MCC placement: where surge protection is commonly applied

The most useful illustration for a plant or municipal site is not a generic building. It is the electrical path: incoming service protection to reduce larger utility-side events, MCC or distribution protection close to motor-control equipment, and branch or control-panel protection near PLCs, drives, power supplies, and communications.

Grounding, bonding, and installation details decide effectiveness

An SPD needs a low-impedance path to divert transient energy. Long leads, poor bonding, corroded connections, separated grounding systems, or poor routing can reduce performance even when the device itself is appropriate.

  • Keep SPD conductors short and direct.
  • Bond control-panel enclosures correctly.
  • Verify grounding-electrode connections and interbuilding bonding.
  • Address shield grounding and cable routing.
  • Separate sensitive wiring from high-energy conductors where practical.

Inspection should be part of maintenance

Surge protective devices can absorb or divert repeated transient events over time. Many industrial devices include visual status indication, replaceable modules, remote alarm contacts, end-of-life indication, or monitoring points that can be wired into PLC or SCADA systems.

That status is especially useful at unmanned lift stations, well houses, and remote telemetry sites. Operators should know when a module needs inspection or replacement instead of assuming the site remains protected after storms or utility disturbances.

Selection factors

  • System voltage and phase configuration
  • Grounding configuration and installation location
  • Short-circuit current rating and available fault current
  • Maximum continuous operating voltage and voltage protection rating
  • Signal type, communication speed, and environment
  • Remote monitoring needs and upstream/downstream coordination

Standards and product evaluation

UL 1449 is the primary North American product safety standard associated with low-voltage SPDs. A listed or evaluated device still has to be selected and installed for the actual electrical system, signal type, environment, and maintenance expectation.

UL Solutions surge protection device testing and certification

How BEA can help

Britton Electronics & Automation can evaluate surge-protection needs during a new control-system design, panel replacement, facility upgrade, or preventative-maintenance inspection. BEA can help identify surge-entry paths across electrical services, PLC cabinets, VFD panels, water and wastewater sites, remote telemetry, instrumentation, Ethernet networks, radio systems, outdoor wiring, and existing grounding and bonding systems.

BEA can also incorporate surge-device status contacts into PLC or SCADA systems so operators receive an alarm when protection needs attention. Surge protection cannot prevent every electrical failure, but a properly designed and maintained system can reduce avoidable damage, unexplained control problems, and costly downtime.

Phoenix Contact surge protection for North American supply systems


Page 3 of 13 • 85 news articles